Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Manual Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Circuit Breakers & Switch /Outdoor Circuit Breakers
LW8A-40.5 Voltage AC SF6 Circuit Breaker
Name | Data | |
Rated voltage | 40.5 | |
Rated current(A) | 1600/2000 | |
Rated Insulate level | Power frequency withstand voltage(kV)1min | 95 |
Thunder impulse withstand vltage (kV) | 185 | |
Rated short-circuit breaking current(kA) | 25/31.5 | |
Rated outof-phase breaking current (kA) | 7.9/10 | |
breaking current of earth fault in different phase(kA) | 27.4/34.8 | |
Rated breaking current of single capacitor bank(A) | 400 | |
Rated Operating sequence | O-0.3S-CO-180S-CO | |
Rated SF6 gas pressure(Mpa) | 0.5 | |
Switch-off time(on rated voltage)(ms) | 30≤t≤40 | |
Switch-on time(on rated voltage)(ms) | 60≤t≤80 | |
Rated short-circuit making current(peak) (kA) | 63/80 | |
Rated short-circuit duration (s) | 4 | |
Rated short-circuit with stand current (kA) | 25/31.5 | |
Rated peak value withstand current(kA) | 63/80 | |
Mechanical life (time) | 10000 | |
Cumulative breaking times of rated short-circuit breaking current 31.5 kA/40kA(time) |
20 | |
Cumulative breaking times of rated current(time) | 2000 | |
Annual leakAge rate of SF6(%) | ≤0.5 | |
Water content of SF6(V\V)(PPm) | ≤150 | |
Outer insulating leakAge ratio distance(mm/kV) | ≥25,≥31 | |
Weight of the circuit breaker(KG) | 1000 |