Outdoor High Voltage Porcelain Expulsion 12kv 100A Dropout Fuse

Product Details
Customization: Available
Breaking Capacity: High
Type: Current Fuse
Manufacturer/Factory, Trading Company
Diamond Member Since 2021

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Plant Area
101~500 square meters
Management System Certification
ISO 9001
  • Outdoor High Voltage Porcelain Expulsion 12kv 100A Dropout Fuse
  • Outdoor High Voltage Porcelain Expulsion 12kv 100A Dropout Fuse
  • Outdoor High Voltage Porcelain Expulsion 12kv 100A Dropout Fuse
  • Outdoor High Voltage Porcelain Expulsion 12kv 100A Dropout Fuse
  • Outdoor High Voltage Porcelain Expulsion 12kv 100A Dropout Fuse
  • Outdoor High Voltage Porcelain Expulsion 12kv 100A Dropout Fuse
Find Similar Products

Basic Info.

Model NO.
DOF12100C320
Usage
High Voltage
Shape
Circle
Fusing Speed
FF
Fusing Device
Pop-up Solid
Standard
IEC
Transport Package
Carton Box
Specification
JDO
Trademark
Jecsany
Origin
China
HS Code
8535100000
Production Capacity
20000PCS/Year

Product Description

 

Principle and Function of Fuse Cut Out
The high-voltage drop-out fuse consists of three parts: insulating support, dynamic and static contacts, and fuse tube. The static contacts are installed at both ends of the insulating support, and the fuse tube is composed of an inner arc suppression tube and an outer phenolic paper tube or epoxy glass fiber cloth tube.

Drop-out fuses are suitable for power systems with a frequency of 50/60Hz and a rated voltage of 35KV and below, and are installed on the high-voltage side of distribution transformers or on the main lines of distribution. The main function is where the protection performance is not high, it can be used in conjunction with the isolating switch to replace the automatic air switch; it can also be used in conjunction with the load switch to replace the expensive circuit breaker. It also has short circuit protection, overload and isolation circuits.

Technical Parameter Table

Type Unit DOF12100C320
Rated Voltage KV 12
Rated Current A 100
Rated Short-circuit Breaking Current KA 8
Impulse Withstand Voltage (BIL) KV 110
Power Frequency withstand Voltage KV 35
Creepage Distance mm 320
Weight kg 6.7
Applicable Standard    IEC 60282-2
Package Size cm 49*28.5*11.5


Application of Cutouts
Outdoor High Voltage Porcelain Expulsion 12kv 100A Dropout Fuse

Outdoor High Voltage Porcelain Expulsion 12kv 100A Dropout FuseOutdoor High Voltage Porcelain Expulsion 12kv 100A Dropout FuseOutdoor High Voltage Porcelain Expulsion 12kv 100A Dropout FuseOutdoor High Voltage Porcelain Expulsion 12kv 100A Dropout FuseOutdoor High Voltage Porcelain Expulsion 12kv 100A Dropout Fuse
More Products:
Outdoor High Voltage Porcelain Expulsion 12kv 100A Dropout Fuse
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier