Audited by an independent third-party inspection agency

Vacuum circuit breaker utilizes vacuum interrupter technology, featuring high breaking capacity, long service life and maintenance-free operation, making it the most ideal protection and control device for medium voltage power systems .
ZN63A-12 (VS1) type indoor high voltage vacuum circuit breaker (hereinafter referred to as circuit breaker) is used for indoor high voltage switch equipment of power system, as a protection and control unit of network equipment, industrial and mining enterprises power equipment, suitable for the place of frequent operation at rated working current or many times of breaking short-circuit current place.
| ZN63A-12 | |||
| Number | Items | Unit | Data |
| 01 | Rated voltage | kV | 40.5 |
| 02 | Rated current | A | 630/1250 |
| 03 | Rated frequency | Hz | 50 or 60 |
| 04 | Rated short circuit breaking current | kA | 25/31.5 |
| 05 | Rated peak withstand current | kA | 63/80 |
| 06 | short-time withstand current(4s) | kA | 25/31.5 |
| 07 | Rated short circuit breaking current (maximum) | kA | 63/80 |
| 08 | Mechanical life | Times | 10000 |
| 09 | Rated Short-circuit Breaking Current Breaking Times | Times | 30 |
| 10 | Power frequency withstand voltage (1min):Phase to phase/earth | kV | 80/95 |
| 11 | Lightning impulse withstand voltage(Phase to phase/earth) | kV | 185 |
| 12 | Secondary Circuit AC Withstand Voltage (1min) | kV | 2 |
| 13 | Rated operating sequence | OC-0.1s-CO-3S-CO-6s-CO-60s restore | |
| 14 | mechanism control voltage | V | AC/DC220 |
| 15 | contact opening distance | mm | 16±1 |
| 16 | Exceed range(the compress length of contact sping) | mm | 4±0.5 |
| 17 | Average break speed | m/s | 1.4~1.8 |
| 18 | Average closing speed | m/s | 0.4~0.8 |
| 19 | The jump time of contact close break | ms | ≤5 |
| 20 | phase-to-phase center distance | mm | 460±2 |
| 21 | Different period of three-phase break and close break | ms | ≤2 |
| 22 | Resistance of each phase main loop | μΩ | <80 |
| 23 | Opening time | ms | ≤100 |
| 24 | Closing time | ms | ≤50 |