Customization: | Available |
---|---|
Application: | Power |
Phase: | Three |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
DESCRIPTION | Unit | SPECIFICATION |
Rated power | kVA | 200 |
Frequency | Hz | 50 |
Maximum Continuous System withstand Voltage | kV | 24 |
Impedance voltage at rated power | % | 4.5 |
Power frequency withstand voltage | kV(rms) | 50 |
Rated lightning, impulse withstand voltage | kV(peak) | 125 |
Power frequency withstand voltage | kV(rms) | 3 |
Rated lightning, impulse withstand voltage | kV(peak) | 6 |
Magnetic flux density (at rated voltage and frequency) | Tesla | 1.7 |
Core Material | CRGO/Amorphous | |
Ambient temperature (max.) | °C | 45 |
Ambient temperature (average) | °C | 30 |
oil/ top | °C | 55 |
windings/ average | °C | 60 |
windings hot spot | °C | 68 |
No -Ioad loss at rated voltage and frequency | k W | ≤0.25 |
Full load loss, W | k W | ≤2.8 |
Rated Current | A | 630 |
Min. creep age distance | mm | 60 |