Mlpd35-D Multi-Chamber Arc Blowing Type Line Protection Device 35kv

Product Details
Type: Power Source Arrester
Structure: Multi-Chamber Arc Blowing Type
Installation: Pole Mounted
Find Similar Products

Basic Info.

Model NO.
MLPD35-D
Application
Power Line Distrubution
Size
Meidum
Operation Voltage
High Voltage
Shape
Spiral
Material
Polymer
Certification
ISO9001
Brand
Jecsany
Transport Package
Carton Box
Specification
MLPD24-C
Trademark
Jecsany
Origin
China
HS Code
8535400000
Production Capacity
10000PCS/Year

Product Description

Specification

1.Highest voltage for equipment can be up to 40.5 kV.

2.Maximum prospective fault current 5.0 kA

3.Lightning discharge capability 2.8 C

4.Installation 1, 2 or 3 pcs per pole

5.Protects from Direct Lightning Strike (DLS)

6.Protects from Back Flashover (BFO)

7.No maintenance is required

 

Usage and Expected Lifespan

1.This device is designed to protect power supply networks from the consequences of either direct lightning strikes or induced overvoltages. Indented to be installed along the protected line, it works perfectly on distribution lines with the highest voltage of equipment up to 40.5 kV.

2.The expected lifespan is up to decades.

 

Operational Principle

MLPD35-D can easily be adapted to any cross-arm or pole configuration. This is possible due to different attaching solutions and accessories available.

 

Parameters

Description

Unit

Value

Electrical line parameters

   

Highest voltage for equipment 1)

kV

40.5

Maximum prospective fault current

kA

5

External air gap

mm

110-180

50% flashover voltage

kV

230

Power frequency withstand voltage 2)

kV (wet/dry)

65/80

Lightning parameters

   

Lightning discharge capability  (200 μs) 3)

C

2.8

High current impulse (4/10 μs)

kA

65

Maximum quenching lightning current

kA

20 (8/50µs)

Minimum withstand amount of operations

 

10

General Parameters

   

Additional power losses on the line

%

0

Average expected lifespan

years

30

UV resistance 4

h

1000

Weight

kg

5.6

Maintenance

 

1 visual verification per year

 

1)According to IEC 60038, 2)According to IEC 60071-1, 3)According to  IEC 60099-8, 4)According to ISO 4892-2, method A, IEC 62217

 