Normal service conditions: 1.The ambient temperature: -40°C ~+40°C 2.The altitude above sea level :not exceed 1000-2000m (the altiplano area should be indicated when order) 3.Earthquake intensity: not higher than 7 degrees; 4.Maximum wind velocity :less than 35m/s. 5.The filthy area should be given clear indication. |
Feature: The zinc oxide surge arrester is the most advanced over-voltage protector in the world. Due to make the resistor disc of core component mainly adopt zinc oxide arrester. Compared with the conventional siliconcarbide arrester, this prescription of the product improves greatly the volt-ampere characteristics of the resistor disc and increase through- current capability at over-voltage so as to bring a rad local-changes for the characteristics of the arresters. |
Products Parameter (Specification)
10kA Series
Arrester type | Rated voltage Ur (kV) | Max. continues operating voltage | Residual Voltage (kV) | |||
as per IEC | as per ANSI/IEEE | 1/10 μs Steep current impuse | 8/20μs Lightning current impulse | 30/60μs Switching current impulse | ||
Uc (kV) | MCOV (kV) | |||||
Y10W-3/9 | 3 | 2.4 | 2.55 | 11.3 | 9 | 8.9 |
Y10W-6/18 | 6 | 4.8 | 5.1 | 20.5 | 18 | 16 |
Y10W-9/27 | 9 | 7.2 | 7.65 | 31 | 27 | 24 |
Y10W-10.5/30 | 10.5 | 8.4 | 9.3 | 36.3 | 31.5 | 27.6 |
Y10W-11/33 | 11 | 8.8 | 9.35 | 38 | 33 | 29 |
Y10W-12/36 | 12 | 9.6 | 10.2 | 41.5 | 36 | 30.6 |
Y10W-15/45 | 15 | 12.0 | 12.7 | 52 | 45 | 38.3 |
Y10W-18/54 | 18 | 14.4 | 15.3 | 62 | 54 | 46 |
Y10W-21/63 | 21 | 16.8 | 17 | 72.5 | 63 | 53.5 |
Y10W-24/72 | 24 | 19.2 | 19.5 | 82.5 | 72 | 61.2 |
Y10W-27/81 | 27 | 21.6 | 22 | 93.2 | 81 | 69 |
Y10W-30/90 | 30 | 24.0 | 24.4 | 104 | 90 | 80 |
Y10W-33/99 | 33 | 26.4 | 28.0 | 113.8 | 99 | 84.2 |
Y10W-36/108 | 36 | 28.8 | 29.0 | 124.2 | 108 | 91.8 |
5kA Series
Arrester type | Rated voltage Ur (kV) | Max. continues operating voltage | Residual Voltage (kV) | |||
as per IEC | as per ANSI/IEEE | 1/10 μs Steep current impuse | 8/20μs Lightning current impulse | 30/60μs Switching current impulse | ||
Uc (kV) | MCOV (kV) | |||||
Y5W-3/9 | 3 | 2.4 | 2.55 | 11.3 | 9 | 8.9 |
Y5W-6/18 | 6 | 4.8 | 5.1 | 20.5 | 18 | 16 |
Y5W-9/27 | 9 | 7.2 | 7.65 | 31 | 27 | 24 |
Y5W-10/30 | 10 | 8.0 | 9.3 | 34.1 | 30 | 26.6 |
Y5W-11/33 | 11 | 8.8 | 9.35 | 38 | 33 | 29 |
Y5W-12/36 | 12 | 9.6 | 10.2 | 41.5 | 36 | 30.6 |
Y5W-15/45 | 15 | 12.0 | 12.7 | 52 | 45 | 38.3 |
Y5W-18/54 | 18 | 14.4 | 15.3 | 62 | 54 | 46 |
Y5W-21/63 | 21 | 16.8 | 17 | 72.5 | 63 | 53.5 |
Y5W-24/72 | 24 | 19.2 | 19.5 | 82.5 | 72 | 61.2 |
Y5W-27/81 | 27 | 21.6 | 22 | 93.2 | 81 | 69 |
Y5W-30/90 | 30 | 24.0 | 24.4 | 104 | 90 | 80 |
Y5W-33/99 | 33 | 26.4 | 28.0 | 113.8 | 99 | 84.2 |
Y5W-36/108 | 36 | 28.8 | 29.0 | 124.2 | 108 | 91.8 |