Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Manual Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
This VCB series adopts advanced vacuum interrupter technology and high-quality ceramic housing, demonstrating excellent breaking performance and electrical endurance. Suitable for power system protection and control in power plants, substations and industrial facilities, it features reliable operation even under frequent switching conditions. Compliant with international standards, it's a key component for modern smart grids.
0 | ltem | Units | Technical parameters | ||
1 | Rated voltage | KV | 12 | ||
2 | Rated short-duration power frequency withstand voltage | 42/48(Interphase,ground/fracture) | |||
3 | Rated lightning impulse withstand voltage | 42/48(Interphase,ground/fracture) | |||
4 | Rated frequency | Hz | 50 | ||
5 | Rated current | A | 630 1250 | 63012501600200025003150 | 63012501600200025003150 |
6 | Rated short-circuit breaking current | KA | 20/25 | 31.5 | 40 |
7 | Rated short-time withstand voltage | 20/25 | 31.5 | 40 | |
8 | Rated short circuit duration | S | 4 | ||
9 | Rated peak withstand current | KA | 50/63 | 80 | 100 |
10 | Rated short circuit closing current | 50/63 | 80 | 100 | |
11 | Secondary circuit power frequency withstand voltage(1min) | 2000 | |||
12 | Rated single /back to back capacitor group breaking current | A | 630/400(40kA:800/400) | ||
13 | Rated capacitor bank closing current | 12.5(frequency is not greater than) | |||
14 | Mechanical life | KA | 20000 | ||
15 | Rated current breaking times(electrical life) | 20000 | |||
16 | Rated short circuit current breaking times | times | 50(40KA≤30) | ||
17 | Dynamic and static contacts allow wear cumulative thickness | mm | 3 | ||
18 | Energy storage time | S | ≤10 | ||
19 | Contact opening distance | mm | 11±1 | ||
20 | overtravel | 3.5±0.5 | |||
21 | Contact closing bounce time | ms | ≤2(40KA≤3) | ||
22 | Three-phase split/closed period | ≤2 | |||
23 | Average opening speed (contacts are separated by-8mm) | m/s | 1.2±0.2 | ||
24 | Main conductive loop resistance | 0.6±0.2 | |||
25 | Main conductive loop resistance | μΩ | ≤50(630A)=45(1250A) ≤40(1600,2000A)≤35(2500A or more) |
||
26 | Rated operation sequence | 0-0.3s-Co-180s-Co |