Item No. |
Description |
Unit |
Module R | Module F | ||||||
Ring Cells | Fuse Protection Cell | |||||||||
Disconnector | Grounding | Fuse Disconnectorl | Grounding | |||||||
1 | Nominal Voltage | kV | 12 | 24 | 12 | 24 | 12 | 24 | 12 | 24 |
2 | Switching Impulse Test Voltage | kV | 28 | 50 | 28 | 50 | 28 | 50 | 28 | 50 |
3 | Nominal Impulse Voltage | kV | 95 | 125 | 95 | 125 | 95 | 125 | 95 | 125 |
4 | Nominal Current | A | 630 | 630 | 630 | 630 | 630 | 630 | 630 | 630 |
5 | Cutting Capacity | |||||||||
5.1 | Full Load | A | 630 | 630 | 200 | 200 | ||||
5.2 | Closed Circuit | A | 670 | 670 | ||||||
5.3 | Cable Loading at No Load | A | 141 | 141 | ||||||
5.4 | Transformer Loading at No Load | A | 20 | 20 | ||||||
5.5 | Ground Fault | A | 205 | 160 | ||||||
5.6 | Cable Loading at Ground Fault | A | 117 | 91 | ||||||
5.7 | Short-Circuit Breaking Current | kA | Fuse Information | |||||||
6 | Manufacturing Capacity | kA | 50 | 50 | 50 | 50 | Fuse Information | 12.5 | 12.5 | |
7 | Short-Time Allowable Current (0.5s) | kA | ||||||||
8 | Short-Time Allowable Current (1s) | kA | 5 | 5 | ||||||
9 | Short-Time Allowable Current (3s) | kA | 20 | 16 | 20 | 16 | ||||
10 | Insulation | SF6 | SF6 | SF6 | SF6 | SF6 | SF6 | SF6 | SF6 |