Nom.Cross-section Area |
Class of Conductor |
Insulation Thickness |
Mean.0.D. | Insulation Min. Resistance at 70°C |
Conductor Max. Resistance at 20°C |
Approx. Weight | |
mm2 | mm | mm | Lower Limit | Upper Limit | MΩ-km | Ω/km | Kg/km |
mm | mm | ||||||
35 | 2 | 1.2 | 9.0 10.9 | 0.0043 | 0.524 | 381 | |
50 | 2 | 1.4 | 10.6 12.6 | 0.0035 | 0.387 | 521 | |
70 | 2 | 1.4 | 12.1 14.6 | 0.0032 | 0.286 | 734 | |
95 | 2 | 1.6 | 14.1 17.1 | 0.0032 | 0.193 | 962 | |
120 | 2 | 1.6 | 15.6 18.8 | 0.0032 | 0.153 | 1180 | |
150 | 2 | 1.8 | 17.3 20.9 | 0.0032 | 0.124 | 1470 | |
185 | 2 | 2.0 | 19.3 23.3 | 0.0032 | 0.0991 | 1810 | |
240 | 2 | 2.2 | 22.0 26.6 | 0.0032 | 0.0754 | 2350 | |
300 | 2 | 2.4 | 24.5 29.6 | 0.0030 | 0.0601 | 2930 | |
400 | 2 | 2.6 | 27.5 33.2 | 0.0028 | 0.0470 | 3870 |