Content | Unit | C Module | F Module | V Module | CB Module | |||
Load Switch | Load Switch with Fuse | Vacuum Switch | Disconnector/Earthing Switch | Vacuum Switch | Disconnector/Earthing Switch | |||
Rated Voltage | kV | 12 | ||||||
Rated Frequency | Hz | 50/60 | ||||||
Power Frequency Withstand voltage in 1 min | kV | 42/48 | ||||||
Lightning impulse Withstand voltage (Peak) | kV | 75/85 | ||||||
Rated Current | A | 1250/630 | Note1 | 1250/630 | - | 1250/630 | - | |
Rated Closed Loop Breaking Current | A | 630 | - | - | - | - | - | |
Rated Cable Charging Breaking Current | A | 10 | - | - | - | - | - | |
Rated Short Circuit Making Current | A | 50 | 80 | 50 | 50 | 63 | 63 | |
Rated Peak Withstand Current | kA | 50 | - | 50 | - | 63 | - | |
Rated Short Circuit Breaking Current | kA/3S | 20 | - | 20 | - | 25 | - | |
Rated Short Circuit Breaking Current | kA | - | 31.5 | 20 | - | 25 | - | |
Rated Transfer Current | A | - | 1700 | - | - | - | - | |
Max. Rated current of fuse | A | - | 125 | - | - | - | - | |
Loop Resistance | μΩ | ≤300 | ≤600 | |||||
Mechanical Life | times | 5000 | 3000 | 5000 | 2000 | 5000 | 5000 | |