Item | Unit | Reference value | LBFCO24200C320 | |
Rated Voltage | KV | 12 | 24 | |
Rated insulation level |
Power frequency voltage (when losing a circuit) |
KV | Breaker 42 | 200 |
Impulse withstand voltage (when losing a circuit) |
KV | Breaker 75 | 10 | |
Rated frequency | Hz | 50/60 | 125 | |
Rated current | A | 630/1250/1600/2000/2500/3150/4000 | ||
Rated short-circuit breaking current | KA | 20,25,31.5,40 | 50 | |
Rated short-circuit making current (peak value) | KA | 50,63,80,100 | 320(360) | |
Rated short-time withstand current | KA | 20,25,31.5,40 | ||
Rated withstand current (peak value) | KA | 50,63,80,100 | ||
Required operation sequence | O-0.3s-CO-180s-CO | |||
Rated short-circuit duration | S | 4 | ||
Times of making-breaking with the rated short-circuit current | Times | 30 | 8.8 | |
Mechanical life | Times | 10000 | IEC 60282-2 | |
Weight | KG | 110 | 53*41.5*19 |
Item | Unit | Reference value |
Gap of contacts | mm | 11±1 |
Contact overtravel | mm | 3.5±0.5 |
Average making speed | m/s | 0.6±0.2 |
Average breaking speed | m/s | 1.1±0.2 |
Bounce time in contact making | ms | ≤2 |
Non-synchronous making/breaking of contact | ms | ≤2 ≤3(40kA) |
Resistance of the circuit of each phase | mΩ | ≤80 |
Permissible total wear thickness of the moving/fixed contact | mm | 3 |
Packaging Details | Wooden Box |
Port | Ningbo Port, Shanghai Port |