| Customization: | Available |
|---|---|
| Certification: | ISO9001 |
| Voltage Level: | Medium Voltage |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| Item | Unit | KYN28A-12 | KYN28A-24 | |
| Rated Voltage | KV | 12 | 24 | |
| Rated Current | A | 630-4000 | 630-4000 | |
| Rated Frequency | HZ | 50/60 | 50/60 | |
| Power Frequency Withstand Voltage in 1 min | Phase.Earthed | KV | 42 | 42 |
| Isolating Fracture | KV | 48 | 48 | |
| Lightning lmpulse Withstand oltage (Peak) | Phase,Earthed | KV | 75 | 75 |
| Isolating Fracture | KV | 85 | 85 | |
| Rated Current of the Main Busbar | A | 630~4000 | 630~4000 | |
| Rated Current of the Branch Busbar | A | 630~4000 | 630~4000 | |
| Rated Short-circuit Breaking Current | KA | 20/25/31.5/40/50 | 20/25/31.5/40/50 | |
| Rated Short Circuit Making Current | KA | 50/63/80/100/125 | 50/63/80/100/125 | |
| Rated Short-time Withstand Current(4s) | KA | 20/25/31.5/40/50 | 20/25/31.5/40/50 | |
| Rated Peak Withstand Current | KA | 50/63/80/100/125 | 50/63/80/100/125 | |
| Frequency Withstand Voltage in 1 min of Aux Control Loop | V | 2000 | 2000 | |
| Intenal Arc Duration Test(0.5s) | KA | 31.5~40 | 31.5~40 | |
| Rated Voltage of Aux Control Loop | V | AC or DC 110/220 | AC or DC 110/220 | |
| Degrees of Protection | IP | P4X(IP2X when the front door is opened) | P4X(IP2X when the front door is opened) | |