Customization: | Available |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Item | Unit | KYN28A-12 | KYN28A-24 | |
Rated Voltage | kV | 12 | 24 | |
Rated Current | A | 630~4000 | 630~4000 | |
Rated Frequency | Hz | 50/60 | 50/60 | |
Power Frequency Withstand Voltage in 1 min |
Phase. Earthed | kV | 42 | 42 |
Isolating Fracture |
kV | 48 | 48 | |
Lightning Impulse Withstand oltage(Peak) |
Phase. Earthed | kV | 75 | 75 |
Isolating Fracture |
kV | 85 | 85 | |
Rated Current of the Main Busbar | A | 630~4000 | 630~4000 | |
Rated Current of the Branch Busbar | A | 630~4000 | 630~4000 | |
Rated Short-circuit Breaking Current | kA | 20/25/31.5/40/50 | 20/25/31.5/40/50 | |
Rated Short Circuit Making Current | kA | 50/63/80/100/125 | 50/63/80/100/125 | |
Rated Short-time Withstand Current(4s) | kA | 20/25/31.5/40/50 | 20/25/31.5/40/50 | |
Rated Peak Withstand Current | kA | 50/63/80/100/125 | 50/63/80/100/125 | |
Frequency Withstand Voltage in 1 min of Aux Control Loop | V |
2000 |
2000 |
|
Intenal Arc Duration Test(0.5s) | kA | 31.5~40 | 31.5~40 | |
Rated Voltage of Aux Control Loop | V | AC or DC 110/220 | AC or DC 110/220 | |
Degrees of Protection | IP | IP4X(IP2X when the front door is opened) | IP4X(IP2X when the front door is opened) |