Customization: | Available |
---|---|
Application: | Power |
Phase: | Three |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Description | Minimum Requirements | |
Unit | Data | |
Rated power | kVA | 2500 |
Rated primary voltage | kV | 12 |
Rated secondary voltage | kV | 0.46 |
Highest system voltage - HV | kV | 14.4 |
Highest system voltage - LV | kV | 0.55 |
Phases | 3 | |
Type of cooling | ONAN | |
Type of bushings | Porcelain | |
Frequency | Hz | 50 |
Maximum over all dimensions | ||
length | mm | 2420 |
width | mm | 1510 |
height | mm | 1810 |
Winding material | ||
HV | aluminium | |
LV | aluminium | |
Impedance voltage | % | 5.00% |
Maximum losses at rated voltage & frequency |
||
No load | W | 2930 |
Full load | W | 27950 |
Temperature rise at rated voltage and power of |
||
Windings | °C | 65 |
Top oil | °C | 60 |
Ambient temperature | °C | -30 to 50 |
Relative humidity range | % | 20-100 |
Altitude above sea level (max.) | m | 1200 |
Power frequency wet withstand voltage |
0.46 kV r.m.s. |
5 |
Tapings | 5 tapings in steps of 2.5% (-5%, -2.5%, 0, +2.5%, +5%) |