Customization: | Available |
---|---|
Application: | High-voltage |
Material: | FRP/GRP |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Characteristics of glass insulators
Small size, light weight, zero-value self-breaking, and easy detection; high mechanical strength; good arc resistance; good self-cleaning performance and not easy to age. In addition, the spraying material has the advantages of strong hydrophobicity, long-term resistance to pollution, low leakage current on the surface, and maintenance-free during operation; it is widely used in various circuits at home and abroad.
Product Model | U40B/110 | U70B/140 | U100B/140 | U120B/146 | U160B/170 | |
Main dimension,mm | D | 178 | 255 | 255 | 255 | 280 |
H | 110 | 140 | 146 | 146 | 170 | |
Creepage distance(mm) | 185 | 320 | 320 | 320 | 400 | |
Socket Coupling(mm) | 11 | 16 | 16 | 16 | 20 | |
Mechanical failing load( mm) | 40 | 70 | 100 | 120 | 160 | |
Mechanical routne test(kN) | 20 | 35 | 50 | 60 | 80 | |
Wetpower frequency withstand voltage(kV) | 25 | 40 | 40 | 40 | 45 | |
Dry lightning lipulse withstand voltage(kV) | 50 | 100 | 100 | 100 | 110 | |
Impuise puncture volltage(P.U) | 2.8 | 2.8 | 2.8 | 2.8 | 2.8 | |
Power frequency puncture vollage (kV) | 90 | 130 | 130 | 130 | 130 | |
Radio influence voltage(μV) | 50 | 50 | 50 | 50 | 50 | |
Corona visual test (kV) | 18/22 | 18/22 | 18/22 | 18/22 | 18/22 | |
Power frequency electric arc voltage | 0.12s/20kA | 0.12s/20kA | 0.12s/20kA | 0.12s/20kA | 0.12s/20kA |