Customization: | Available |
---|---|
Type: | Power Source Arrester |
Structure: | Zinc Oxide Arrester |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Service condition | |
Rated voltage | 12KV |
MCOV | 11KV |
Nominal discharge current | 10KA |
Creepage distance | 310mm |
Lightening impulse residual Voltage under nomlinal discharge current |
16 |
Lin discharge class | 1 |
2ms square wave impulse current withstand(A) | 250 |
4/10μhigh current impulse withstand(KA) | 100 |
Standard | IEC60099-4 |
Normal service conditions: 1.The ambient temperature: -40°C ~+40°C 2.The altitude above sea level :not exceed 1000-2000m (the altiplano area should be indicated when order) 3.Earthquake intensity: not higher than 7 degrees; 4.Maximum wind velocity :less than 35m/s. 5.The filthy area should be given clear indication. |
Feature: The zinc oxide surge arrester is the most advanced over-voltage protector in the world. Due to make the resistor disc of core component mainly adopt zinc oxide arrester. Compared with the conventional siliconcarbide arrester, this prescription of the product improves greatly the volt-ampere characteristics of the resistor disc and increase through- current capability at over-voltage so as to bring a rad local-changes for the characteristics of the arresters. |